ATEX 400VA TRANSFORMER
The Wolf ATEX transformers are CE marked to the ATEX directive for safe use in Zones 1 potentially explosive gas and 21 dust atmospheres, where the T class and ambient temperatures permit. Wolf transformers are both ATEX and IECEx certified.
Product Information
LL-114/T3, LL-214/T3, LL-221/T3, LL-133/T3, LL-233/T3, LL-243/T3
ZONES: 1, 2, 21 AND 22
Models operating from 230V or 110V to 24V and 230V to 110V, the transformers are intended for use with the Wolf range of temporary ambient and task lights and with ancillary equipment for maintenance tasks. The transformers have 400VA and 320VA dual power rating options allowing them to be safely used in a range of upper operating ambient temperatures depending on power usage.
As standard, Transformers are supplied with a 15 metre input cable fitted with an ATX plug and with four ATX output sockets fitted to the enclosure. The Transformers are available with a stainless steel or GRP enclosure, sealed to IP66, enabling use in wet and dusty conditions. In addition, a stainless steel outer protective skid makes the unit stronger and easier to handle for temporary installations ensuring that it can withstand the harshest of environments.
All Wolf’s ATEX power distribution systems are robust and durable in their construction, compact and portable for easy handling and fully flexible to enable different configurations to be built to your specific hazardous area requirement.
IMPA Code
33 19 01 - LL-133/T3, 33 19 02 - LL-233/T3
-
Certified
ATEX and IECEx certified for use in Zones 1 explosive Gas and 21 explosive Dust atmospheres
-
Different Voltages
Range of voltages available
-
Safe Power!
Supplies Wolf Hazardous Area Temporary ambient and task lighting
Features & Benefits
- ATEX approved for use in Zones 1 explosive gas and 21 dust atmospheres
- IECEx certified
- Robust and durable construction
- Transportable and portable design
- Wide range of voltages available - 230V or 110V to 24V and 230V to 110V
- 400VA and 320VA power rating options
- Fitted with 4 x ATX socket outlets
- Supplied with 15m SY cable and ATX plug
- CEAG, STAHL and Marechal plug options available
- Powers temporary ambient and task lighting
- 110V versions available with CTE (Centre Tap Earth) option
LL-114/T3
Gas Zone: 1 and 2
Dust Zone: 21 and 22
Enclosure: GRP
INPUT / OUTPUT: 110V : 24V
LL-214/T3
Gas Zone: 1 and 2
Dust Zone: 21 and 22
Enclosure: GRP
INPUT / OUTPUT: 230V : 24V
LL-221/T3
Gas Zone: 1 and 2
Dust Zone: 21 and 22
Enclosure: GRP
INPUT / OUTPUT: 230V : 110V
LL-133/T3
Gas Zone: 1 and 2
Dust Zone: 21 and 22
Enclosure: Stainless Steel
INPUT / OUTPUT: 110V : 24V
LL-233/T3
Gas Zone: 1 and 2
Dust Zone: 21 and 22
Enclosure: Stainless Steel
INPUT / OUTPUT: 230V : 24V
LL-243/T3
Gas Zone: 1 and 2
Dust Zone: 21 and 22
Enclosure: Stainless Steel
INPUT / OUTPUT: 230V : 110V
Product Reference | LL-114/T3 | LL-214/T3 | LL-221/T3 | LL-133/T3 | LL-233/T3 | LL-243/T3 |
---|---|---|---|---|---|---|
Product Description | GRP | Stainless Steel | ||||
110V:24V | 230V:24V | 230V:110V | 110V:24V | 230V:24V | 230V:110V | |
Code |
For Output Power ≤ 400VA II2 GD Ex d e IIC T3 Gb For Output Power ≤ 320VA II2 GD Ex d e IIC T3 Gb |
For Output Power ≤ 400VA II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +30°C) For Output Power ≤ 320VA II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +42°C) |
||||
Type of Protection | 'e' increased safety, 'd' flameproof | |||||
Area of Classification (Gas) | Zones 1 and 2, Gas groups IIA, IIB and IIC | |||||
Temperature Class (Gas) | T3 | T3 | ||||
Area of Classification (Dust) | Zones 21 and 22, Dust Groups IIIA, IIIB and IIIC | |||||
Max. Surface Temperature (Dust) | T195°C | T195°C | ||||
Ambient Temperature |
400VA -20°C to +35°C 320VA -20°C to +50°C |
400VA -20°C to +30°C 320VA -20°C to +42°C |
||||
Certificate |
ATEX - LCIE02ATEX6248X IECEX - LCI 04.0016X |
ATEX - LCIE02ATEX6118X IECEX - LCI 11.0008X |
||||
Enclosure | Glass reinforced polyester (GRP) enclosure, marine grade (316L) stainless steel skid | Marine grade (316L) stainless steel enclosure and skid | ||||
Power | 320 / 400VA | 320 / 400VA | ||||
Volts In | 110V ac +6% -10% | 230V ac +6% -10% | 110V ac +6% -10% | 230V ac +6% -10% | ||
Input Cable | 15m SY cable 2.5mm² with ATX 110V / 230V 2P+E plug fitted as standard | |||||
Volts Out | 24V | 110V | 24V | 110V | ||
Socket Arrangement & Configuration |
4 output sockets, ATX 110V / 24V 2P+E as standard | |||||
2 sockets on each unit side | ||||||
Dimensions | 504 x 465 x 285mm (L x W x H) | 512 x 562 x 260 mm (L x W x H) | ||||
Ingress Protection | IP66 | |||||
Weight | 21 Kg | 28 Kg |
- Dual marked GRP Transformer certified T3 with an ambient temperature range of -20°C to +50°C at 320VA power and with an ambient temperature range of -20°C to +35°C at 400VA power.
- Dual marked SS Transformer certified T3 with an ambient temperature range of -20°C to +42°C at 320VA power and with an ambient temperature range of -20°C to +30°C at 400VA power.
- CEAG, Stahl and Marechal plug options and longer SY input cable available on request.
- Ships braided cable for offshore applications to BS6883 available on request.
- Changes may be made to the above specification without notification, details are available on request.
- All information has been gathered under laboratory conditions, the user must regard the values given as approximate.
ATEX 400VA Transformer Product Information Sheet
(PDF, 301 KB)
Wolf ATEX 400VA/320VA and 250 VA GRP Transformer Operation and Maintenance Instructions
(PDF, 862 KB)
Wolf ATEX 400VA/320VA and 250 VA Stainless Steel Transformer Operation and Maintenance Instructions
(PDF, 146 KB)
ATEX GRP 400VA Transformer - ATEX certificate
(PDF, 625 KB)
ATEX S/S 400VA Transformer - ATEX certificate
(PDF, 3.4 MB)
ATEX S/S 400VA Transformer - IECEx Certificate
(PDF, 715 KB)
ATEX GRP 400VA Transformer - IECEx certificate
(PDF, 303 KB)
Got a question